首页 | 本学科首页   官方微博 | 高级检索  
     检索      

闪电定位资料对仪征储油罐雷灾成因的分析应用
引用本文:冯民学,罗慧,焦雪.闪电定位资料对仪征储油罐雷灾成因的分析应用[J].气象科学,2007,27(6):679-684.
作者姓名:冯民学  罗慧  焦雪
作者单位:1. 江苏省防雷中心,南京,210009
2. 陕西省防雷中心,西安,710015
摘    要:本文根据多普勒天气雷达回波与闪电定位仪资料,结合雷电现场进行实地勘查的结果,探讨2006年8月7日发生在扬州市仪征油罐雷电灾害事故。综合分析发现当时强对流回波达55 dBz、顶高14 km;在距油罐1 km范围内有闪电13次,负电荷集聚、强度多在20~50 kA之间。此次雷灾事故的直接致灾原因是强大的感应雷电脉冲电流在储油罐罐体与浮顶两根连接电缆上产生较大的电压,导致储油罐罐体与浮顶之间在密封处产生闪络,引起油汽外泄燃爆成灾。为减少此类雷电灾害的发生,提出防护建议。

关 键 词:雷电灾害  雷达回波  闪电定位  雷电感应  雷电防护
修稿时间:2007年3月2日

AN APPROACH TO THE CAUSE OF FORMING THE LIGHTNING STRIKE DISASTER OF OIL TANKS IN YIZHENG ACCORDING TO THE LIGHTNING FLASH POSITIONING DATA AND AN APPLICATION
Feng Minxue,Luo Hui,Jiao Xue.AN APPROACH TO THE CAUSE OF FORMING THE LIGHTNING STRIKE DISASTER OF OIL TANKS IN YIZHENG ACCORDING TO THE LIGHTNING FLASH POSITIONING DATA AND AN APPLICATION[J].Scientia Meteorologica Sinica,2007,27(6):679-684.
Authors:Feng Minxue  Luo Hui  Jiao Xue
Abstract:The Yizheng oil tanks in Yangzhou city were struck by stormy lightning on Aug.7,2006.The present article is an approach to the cause of forming a fire disaster arising from the above-said lightning strikes in accordance with the Doppler weather radar echoes and the data shown on the lightning flash positioning indicators,and in accordance with the on-the-spot investigation results recorded at the lightning strike site.An overall analysis indicates: the strong convective echo recorded at that time reached 55 dBz;the cloud top developed to 14km;the lightning was recorded for 13 times within an area 1km away from the oil tanks;and the accumulated minus charge had a strength of 20~50 kA.The immediate cause for the above-said lightning strike disaster lies in the great voltage generated by the strong lightning-induced impulse current at two cables for connecting an oil tank body and its floating roof.It is due to this great voltage that a flashover was generated at the airtight seals between the oil tank bodies and their floating roofs.And it is just this flashover that enables the oil and the oil vapour to leak out to catch fire.In order to reduce the occurrence of such lightning strike disasters,we have worked out a protection proposal accordingly.
Keywords:Lightning strike disaster Radar echo Lightning flash positioning Lightning inductance Lightning strike protection
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《气象科学》浏览原始摘要信息
点击此处可从《气象科学》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏