首页 | 本学科首页   官方微博 | 高级检索  
相似文献
 共查询到20条相似文献,搜索用时 15 毫秒
1.
This paper presents the development and validation of a real‐time hybrid simulation (RTHS) system for efficient dynamic testing of high voltage electrical vertical‐break disconnect switches. The RTHS system consists of the computational model of the support structure, the physical model of the insulator post, a small shaking table, a state‐of‐the‐art controller, a data acquisition system and a digital signal processor. Explicit Newmark method is adopted for the numerical integration of the governing equations of motion of the hybrid structure, which consists of an insulator post (experimental substructure) and a spring‐mass‐dashpot system representing the support structure (analytical substructure). Two of the unique features of the developed RTHS system are the application of an efficient feed‐forward error compensation scheme and the ability to use integration time steps as small as 1 ms. After the development stage, proper implementation of the algorithm and robustness of the measurements used in the calculations are verified. The developed RTHS system is further validated by comparing the RTHS test results with those from a conventional shaking table test. A companion paper presents and discusses a parametric study for a variety of geometrical and material configurations of these switches using the developed RTHS system. Copyright © 2013 John Wiley & Sons, Ltd.  相似文献   

2.
This paper presents real‐time hybrid earthquake simulation (RTHS) on a large‐scale steel structure with nonlinear viscous dampers. The test structure includes a three‐story, single‐bay moment‐resisting frame (MRF), a three‐story, single‐bay frame with a nonlinear viscous damper and associated bracing in each story (called damped braced frame (DBF)), and gravity load system with associated seismic mass and gravity loads. To achieve the accurate RTHS results presented in this paper, several factors were considered comprehensively: (1) different arrangements of substructures for the RTHS; (2) dynamic characteristics of the test setup; (3) accurate integration of the equations of motion; (4) continuous movement of the servo‐controlled hydraulic actuators; (5) appropriate feedback signals to control the RTHS; and (6) adaptive compensation for potential control errors. Unlike most previous RTHS studies, where the actuator stroke was used as the feedback to control the RTHS, the present study uses the measured displacements of the experimental substructure as the feedback for the RTHS, to enable accurate displacements to be imposed on the experimental substructure. This improvement in approach was needed because of compliance and other dynamic characteristics of the test setup, which will be present in most large‐scale RTHS. RTHS with ground motions at the design basis earthquake and maximum considered earthquake levels were successfully performed, resulting in significant nonlinear response of the test structure, which makes accurate RTHS more challenging. Two phases of RTHS were conducted: in the first phase, the DBF is the experimental substructure, and in the second phase, the DBF together with the MRF is the experimental substructure. The results from the two phases of RTHS are presented and compared with numerical simulation results. An evaluation of the results shows that the RTHS approach used in this study provides a realistic and accurate simulation of the seismic response of a large‐scale structure with rate‐dependent energy dissipating devices. Copyright © 2015 John Wiley & Sons, Ltd.  相似文献   

3.
An electrical substation consists of a complex set of equipment items that are interconnected through conductor buses or cables. If the connections are not sufficiently flexible, significant dynamic interaction may occur between the connected equipment items during a seismic excitation. This interaction is believed to be responsible for some of the observed substation equipment damage in recent earthquakes. This paper investigates the interaction between two equipment items connected by a linear spring‐dashpot or spring‐dashpot‐mass element representing a conductor bus. It is found that the interaction between the two equipment items may significantly amplify the response of the higher‐frequency equipment item. The influences of various key parameters on the interaction effect are quantified. Means for reducing the adverse interaction effect are described. Copyright © 2001 John Wiley & Sons, Ltd.  相似文献   

4.
This paper presents the results of a parametric study that consists of real‐time hybrid simulation tests of electrical insulator posts on a smart shaking table. A companion paper presents the details of the development and validation of the real‐time hybrid simulation system used for conducting the tests of this parametric study. The purpose of the parametric study presented in this paper is to evaluate the effect of support structure damping and stiffness on the response of disconnect switches with two different insulator materials, namely porcelain and polymer insulator posts. Various global and local response parameters including accelerations, forces, displacements, and strains are considered in this evaluation. The data obtained from the conducted tests show that the maximum insulator response corresponds to the case where the support structure frequency is close to the insulator frequency. An incorporated evaluation of all the response parameters indicates that the stiff support structures constitute the most suitable configuration for both material types of the tested insulator posts. It is also observed that support structure damping has an effect on the response of both insulator types. However, this effect is secondary compared with the effect of support structure stiffness. Copyright © 2013 John Wiley & Sons, Ltd.  相似文献   

5.
A series of large‐scale real‐time hybrid simulations (RTHSs) are conducted on a 0.6‐scale 3‐story steel frame building with magneto‐rheological (MR) dampers. The lateral force resisting system of the prototype building for the study consists of moment resisting frames and damped brace frames (DBFs). The experimental substructure for the RTHS is the DBF with the MR dampers, whereas the remaining structural components of the building including the moment resisting frame and gravity frames are modeled via a nonlinear analytical substructure. Performing RTHS with an experimental substructure that consists of the complete DBF enables the effects of member and connection component deformations on system and damper performance to be accurately accounted for. Data from these tests enable numerical simulation models to be calibrated, provide an understanding and validation of the in‐situ performance of MR dampers, and a means of experimentally validating performance‐based seismic design procedures for real structures. The details of the RTHS procedure are given, including the test setup, the integration algorithm, and actuator control. The results from a series of RTHS are presented that includes actuator control, damper behavior, and the structural response for different MR control laws. The use of the MR dampers is experimentally demonstrated to reduce the response of the structure to strong ground motions. Comparisons of the RTHS results are made with numerical simulations. Based on the results of the study, it is concluded that RTHS can be conducted on realistic structural systems with dampers to enable advancements in resilient earthquake resistant design to be achieved. Copyright © 2014 John Wiley & Sons, Ltd.  相似文献   

6.
为研究铅金属减震器对特高压互连电气设备的减震效果,进行由硬管母线连接的特高压避雷器设备和电容式电压互感器设备组成的互连耦合体系的地震模拟振动台试验。通过白噪声扫频、抗震及减震试验,测定互连耦合体系抗震结构及减震结构的自振频率以及关键部位的应变、加速度响应。试验结果表明:抗震结构中避雷器设备的最大应变响应大于互感器设备,互连耦合体系中的避雷器设备属于易损设备;安装减震器后互连设备频率降低幅度较小,减震器基本不会影响电气设备的正常运行;安装减震器后互连耦合体系中的避雷器设备和互感器设备在较大峰值加速度地震波作用下,设备顶端加速度响应和最大应变响应均有较大幅度的降低,避雷器设备和互感器设备的最大应变响应的减震效率分别为75%和50%,减震效果显著,减震器的应用大幅提升了互连耦合体系的抗震能力。  相似文献   

7.
Real‐time substructuring is a method of dynamically testing a structure without experimentally testing a physical model of the entire system. Instead the structure can be split into two linked parts, the region of particular interest, which is tested experimentally, and the remainder which is tested numerically. A transfer system, such as a hydraulic actuator or a shaking table, is used to impose the displacements at the interface between the two parts on the experimental substructure. The corresponding force imposed by the substructure on the transfer system is fed back to the numerical model. Control of the transfer system is critical to the accuracy of the substructuring process. A study of two controllers used in conjunction with the University of Bristol shaking table is presented here. A proof‐of‐concept one degree‐of‐freedom mass–spring–damper system is substructured such that a portion of the mass forms the experimental substructure and the remainder of the mass plus the spring and the damper is modelled numerically. Firstly a linear controller is designed and tested. Following this an adaptive substructuring strategy is considered, based on the minimal control synthesis algorithm. The deleterious effect of oil‐column resonance common to shaking tables is examined and reduced through the use of filters. The controlled response of the experimental specimen is compared for the two control strategies. Copyright © 2005 John Wiley & Sons, Ltd.  相似文献   

8.
The seismic performance of timber bridge substructures is not well established, particularly when compared to concrete highway bridges. This paper presents a dual experimental‐computational modelling program to investigate the seismic behaviour of typical braced timber bridge pile bents. For this purpose, a prototype timber bridge was used to develop a near‐full‐size physical model that was used for shaking table experiments and quasi‐static reversed cyclic loading tests on the laboratory strong‐floor. A non‐linear force‐displacement computational modelling study was also undertaken as a companion effort to the experimental investigation. On the basis of the experimental study, seismic vulnerability analysis was conducted for this kind of timber bridge principally with shaking in the transverse direction. In this analysis, a simplified fundamental mechanics‐based approach was employed from which fragility curves were derived. The study showed that braced timber pile bents have considerable strength and deformability capability. Nevertheless, they are not immune from earthquake damage. Copyright © 2003 John Wiley & Sons, Ltd.  相似文献   

9.
The time delay resulting from the servo hydraulic systems can potentially destabilize the real‐time dynamic hybrid testing (RTDHT) systems. In this paper, the discrete‐time root locus technique is adopted to investigate the delay‐dependent stability performance of MDOF RTDHT systems. Stability analysis of an idealized two‐story shear frame with two DOFs is first performed to illustrate the proposed method. The delay‐dependent stability condition is presented for various structural properties, time delay, and integration time steps. Effects of delay compensation methods on stability are also investigated. Then, the proposed method is applied to analyze the delay‐dependent stability of a single shaking table RTDHT system with an 18‐DOF finite element numerical substructure, and corresponding RTDHTs are carried out to verify the theoretical results. Furthermore, the stability behavior of a finite element RTDHT system with two physical substructures, loaded by twin shaking tables, is theoretically and experimentally investigated. All experimental results convincingly demonstrate that the delay‐dependent stability analysis on the basis of the discrete‐time root locus technique is feasible. Copyright © 2014 John Wiley & Sons, Ltd.  相似文献   

10.
通过母线连接的电气设备与独立设备地震响应存在较大差异。为定量研究软母线连接体系对设备的地震响应,将软母线简化为悬索结构,建立耦联体系等高设备和单体设备的地震运动方程组,采用龙格-库塔方法计算得到广泛参数下的位移响应比,并通过基于后向消去法的多元回归分析对各关键参数的影响进行量化,得到软母线耦联等高设备地震位移响应比公式。通过与实际振动台试验数据对比验证了该响应比公式的准确性。研究结果可为实际电气设备及变电站的抗震可靠性分析提供参考。  相似文献   

11.
Real‐time hybrid simulation (RTHS) is a powerful cyber‐physical technique that is a relatively cost‐effective method to perform global/local system evaluation of structural systems. A major factor that determines the ability of an RTHS to represent true system‐level behavior is the fidelity of the numerical substructure. While the use of higher‐order models increases fidelity of the simulation, it also increases the demand for computational resources. Because RTHS is executed at real‐time, in a conventional RTHS configuration, this increase in computational resources may limit the achievable sampling frequencies and/or introduce delays that can degrade its stability and performance. In this study, the Adaptive Multi‐rate Interface rate‐transitioning and compensation technique is developed to enable the use of more complex numerical models. Such a multi‐rate RTHS is strictly executed at real‐time, although it employs different time steps in the numerical and the physical substructures while including rate‐transitioning to link the components appropriately. Typically, a higher‐order numerical substructure model is solved at larger time intervals, and is coupled with a physical substructure that is driven at smaller time intervals for actuator control purposes. Through a series of simulations, the performance of the AMRI and several existing approaches for multi‐rate RTHS is compared. It is noted that compared with existing methods, AMRI leads to a smaller error, especially at higher ratios of sampling frequency between the numerical and physical substructures and for input signals with high‐frequency content. Further, it does not induce signal chattering at the coupling frequency. The effectiveness of AMRI is also verified experimentally. Copyright © 2016 John Wiley & Sons, Ltd.  相似文献   

12.
Real‐time hybrid simulation (RTHS) has increasingly been recognized as a powerful methodology to evaluate structural components and systems under realistic operating conditions. It is a cost effective approach compared with large scale shake table testing. Furthermore, it can maximally preserve rate dependency and nonlinear characteristics of physically tested (non)structural components. Although conceptually very attractive, challenges do exist that require comprehensive validation before RTHS should be employed to assess complicated physical phenomena. One of the most important issues that governs the stability and accuracy of an RTHS is the ability to achieve synchronization of boundary conditions between the computational and physical substructures. The objective of this study is to propose and validate an H loop shaping design for actuator motion control in RTHS. Controller performance is evaluated in the laboratory using a worst‐case substructure proportioning scheme. A modular, one‐bay, one‐story steel moment resisting frame specimen is tested experimentally. Its deformation is kept within the linear range for ready comparison with the reference closed‐form solution. Both system analysis and experimental results show that the proposed H strategy can significantly improve both the stability limit and test accuracy compared with several existing strategies. Another key feature of the proposed strategy is its robust performance in terms of unmodeled dynamics and uncertainties, which inevitably exist in any physical system. This feature is essential to enhance test quality for specimens with nonlinear dynamic behavior, thus ensuring the validity of the proposed approach for more complex RTHS implementations. Copyright © 2012 John Wiley & Sons, Ltd.  相似文献   

13.
Real‐time hybrid simulation (RTHS) is increasingly being recognized as a powerful cyber‐physical technique that offers the opportunity for system evaluation of civil structures subject to extreme dynamic loading. Advances in this field are enabling researchers to evaluate new structural components/systems in cost‐effective and efficient ways, under more realistic conditions. For RTHS, performance metric clearly needs to be developed to predict and evaluate the accuracy of various partitioning choices while incorporating the dynamics of the transfer system, and computational/communication delays. In addition, because of the dynamics of the transfer system, communication delays, and computation delays, the RTHS equilibrium force at the interface between numerical and physical substructures is subject to phase discrepancy. Thus, the transfer system dynamics must be accommodated by appropriate actuator controllers. In this paper, a new performance indicator, predictive performance indicator (PPI), is proposed to assess the sensitivity of an RTHS configuration to any phase discrepancy resulting from transfer system dynamics and computational/communication delays. The predictive performance indicator provides a structural engineer with two sets of information as follows: (i) in the absence of a reference response, what is the level of fidelity of the RTHS response? and (ii) if needed, what partitioning adjustments can be made to effectively enhance the fidelity of the response? Moreover, along with the RTHS stability switch criterion, this performance metric may be used as an acceptance criteria for conducting single‐degree‐of‐freedom RTHS. Copyright © 2014 John Wiley & Sons, Ltd.  相似文献   

14.
In real‐time hybrid simulations (RTHS) that utilize explicit integration algorithms, the inherent damping in the analytical substructure is generally defined using mass and initial stiffness proportional damping. This type of damping model is known to produce inaccurate results when the structure undergoes significant inelastic deformations. To alleviate the problem, a form of a nonproportional damping model often used in numerical simulations involving implicit integration algorithms can be considered. This type of damping model, however, when used with explicit integration algorithms can require a small time step to achieve the desired accuracy in an RTHS involving a structure with a large number of degrees of freedom. Restrictions on the minimum time step exist in an RTHS that are associated with the computational demand. Integrating the equations of motion for an RTHS with too large of a time step can result in spurious high‐frequency oscillations in the member forces for elements of the structural model that undergo inelastic deformations. The problem is circumvented by introducing the parametrically controllable numerical energy dissipation available in the recently developed unconditionally stable explicit KR‐α method. This paper reviews the formulation of the KR‐α method and presents an efficient implementation for RTHS. Using the method, RTHS of a three‐story 0.6‐scale prototype steel building with nonlinear elastomeric dampers are conducted with a ground motion scaled to the design basis and maximum considered earthquake hazard levels. The results show that controllable numerical energy dissipation can significantly eliminate spurious participation of higher modes and produce exceptional RTHS results. Copyright © 2014 John Wiley & Sons, Ltd.  相似文献   

15.
It is well known that real‐time hybrid simulation (RTHS) is an effective and viable dynamic testing method. Numerous studies have been conducted for RTHS during the last 2 decades; however, the application of RTHS toward practical civil infrastructure is fairly limited. One of the major technical barriers preventing RTHS from being widely accepted in the testing community is the difficulty of accurate displacement control for axially stiff members. For such structures, a servo‐hydraulic actuator can generate a large force error due to the stiff oil column in the actuator even if there is a small axial displacement error. This difficulty significantly restricts the implementation of RTHS for structures such as columns, walls, bridge piers, and base isolators. Recently, a flexible loading frame system was developed, enabling a large‐capacity real‐time axial force application to axially stiff members. With the aid of the flexible loading frame system, this paper demonstrates an RTHS for a bridge structure with an experimental reinforced concrete pier, which is subjected to both horizontal and vertical ground motions. This type of RTHS has been a challenging task due to the lack of knowledge for satisfying the time‐varying axial force boundary condition, but the newly developed technology for real‐time force control and its incorporation into RTHS enabled a successful implementation of the RTHS for the reinforced concrete pier of this study.  相似文献   

16.
地震检波器惯性体的运动方程可以写成: (1) n0为检波器在无阻尼时的固有圆频率,h为检波器的阻尼常数,y为地面的位移。如用动圈检波器,其输出电压E的方程可写成: (2) S=Bl,称为检波器的电磁放大系数,B为所用磁钢空气隙中的磁感量,l为线圈的有效长度。自公式(1)及(2)可以见到:如果知道了检波器的常数h,n0和S,检波器的特性便完全确定;然后我们就可以推算检波器惯性体的运动,或是线圈的输出电压与地面运动  相似文献   

17.
本文采用振动台子结构试验数值仿真验证了圆柱形调谐液体阻尼器(CTLD)控制建筑结构地震响应的性能。振动台子结构试验将结构模型作为数值子结构在计算机中计算,将CTLD作为试验子结构进行物理试验。在CTLD和振动台之间安装剪切力检测装置,将测得的剪切力和地震波输入到数值子结构中,采用实时子结构中心差分法进行数值子结构运动方程的求解,计算得到了结构顶层的绝对加速度。再将加速度由振动台实时加载到试验子结构上,实现了结构和CTLD的相互作用。对一个单自由度结构有CTLD控制和无CTLD控制时的加速度响应进行了精确数值求解,结果验证了CTLD能够有效地控制结构在地震作用下的加速度响应。用振动台子结构试验对CTLD与结构耦合系统进行仿真,得到的加速度响应与精确数值求解的结果吻合较好,验证了这种方法能够准确地评估CTLD的减振性能。  相似文献   

18.
The peer‐to‐peer (P2P) Internet online hybrid test system has been developed for the seismic simulation of a structure. In this study, the stability and accuracy of the system are investigated analytically by studying the spectral radius of the recursive matrix of the test scheme featuring a two‐round quasi‐Newton test scheme. The applicability of the system is further examined by exploring the seismic responses of a complex structure, a steel‐encased reinforced concrete (SRC) structure with a steel tower on the top. The structure is divided into two numerical substructures and one tested part for hybrid test. The numerical substructures are simulated by sophisticated finite element method (FEM) models with material nonlinearities to capture local plastifications. Two types of FEM programs, namely OpenSEES and ABAQUS, which are suitable for the SRC part and the steel tower, respectively, are employed. The results demonstrate that the P2P system is able to simulate complex structures with significant nonlinearities. As compared with the previous study in which two elastic numerical substructures were considered, increase in the number of iterations in this study is not significant, because the associated nonlinearities are limited due to the small time interval adopted in the test. Copyright © 2007 John Wiley & Sons, Ltd.  相似文献   

19.
In this study, a constitutive model of high damping rubber bearings (HDRBs) is developed that allows the accurate representation of the force–displacement relationship including rate‐dependence for shear deformation. The proposed constitutive model consists of two hyperelastic springs and a nonlinear dashpot element and expresses the finite deformation viscoelasticity laws based on the classical Zener model. The Fletcher–Gent effect, manifested as high horizontal stiffness at small strains and caused by the carbon fillers in HDRBs, is accurately expressed through an additional stiffness correction factor α in the novel strain energy function. Several material parameters are used to simulate the responses of high damping rubber at various strain levels, and a nonlinear viscosity coefficient η is introduced to characterize the rate‐dependent property. A parameter identification scheme is applied to the results of the multi‐step relaxation tests and the cyclic shear tests, and a three‐dimensional function of the nonlinear viscosity coefficient η with respect to the strain, and strain rate is thus obtained. Finally, to investigate the accuracy and feasibility of the proposed model for application to the seismic response assessment of bridges equipped with HDRBs, an improved real‐time hybrid simulation (RTHS) test system based on the velocity loading method is developed. A single‐column bridge was used as a test bed and HDRBs was physically tested. Comparing the numerical and RTHS results, advantage of the proposed model in the accuracy of the predicted seismic response over comparable hysteretic models is demonstrated. Copyright © 2016 John Wiley & Sons, Ltd.  相似文献   

20.
导线对电瓷型电气设备地震反应的影响   总被引:1,自引:0,他引:1  
本文利用杆单元大变形有限元方法,探讨了导线对电瓷型电气设备抗震性能的影响,以及通过导线相连的电气设备之间的相互作用。计算分析结果表明:导线会加大设备的应变反应;导线的跨度不同,其对设备动力反应的影响也不同,导线跨度越小,其影响程度越小;导线在振动过程中,内部不但有拉应力,而且存在压应力;导线两端设备相同与不同时,导线对设备动力反应影响程度不同,对频率较高的设备而言,2种情况影响程度差异不大,而对频率较低的设备来讲,2种情况影响程度差异较大。  相似文献   

设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号